59 Generator Phase A Power Factor Lead/Lag Status 30059 0=Current lags voltage, 1=Current leads voltage, 224-255
Fault Identifiers*
60 Generator Phase B Power Factor Lead/Lag Status 30060 0=Current lags voltage, 1=Current leads voltage, 224-255
Fault Identifiers*
61 Generator Phase C Power Factor Lead/Lag Status 30061 0=Current lags voltage, 1=Current leads voltage, 224-255
Fault Identifiers*
62 Generator Average Power Factor Lead/Lag Status 30062 0=Current lags voltage, 1=Current leads voltage, 224-255
Fault Identifiers*
67 EPG Circuit Breaker Status (GSP+P only) 30067 0=Breaker open, 1=Breaker closed, 228=Breaker sensor input
shorted low
151 Engine Coolant Pump Pressure Status 30151 0=coolant pressure OK, 1=coolant pressure too high, 2=Too
Low. 0-223 is Valid Range, 224-255 are Fault Identifiers
200 Hydrax Oil Pressure Switch Status 30200 22=Open, 23=Closed. 65504-65535 are Fault Identifiers
202 Emissions Feedback Mode 30202 394=Combustion Time Feedback, 395=Exhaust Temperature
Feedback, 397=Calibration Feedback, 398=No Feedback,
65504-65535 are Fault Identifiers
Multistate
Read from modbus register as unsigned integer. The value indicates different status conditions depending on
the value being read. See details below:
Monico
Id
PID Description Modbus
Address
Manual Remarks
22 Generator Phase Select 30022 0=Phase A-B Volts A current, 1=Phase B-C Volts B current,
2=Phase C-A Volts C current
25 Generator AC Voltage Full Scale and External PT
Setpoint
30025 0=700v, 1=150v, 2=300, 3=500, 4=600, 5=750, 6=3k,
7=4.5k, 8=5.25k, 9=9k, 10=15k, 11=18k, 12=30k
26 Generator AC Current Full Scale Setpoint (Read) 30026 starting at 0:
75,100,150,200,300,400,600,800,1k,1.2k,1.5k,2k,2.5k,3k,4k
Amps
31 ECM in Control (Marine Only) 30031 0=Primary ECM is controlling, 1=Backup ECM is controlling
57 Generator AC Voltage Full Scale Transformer Setpoint 30057 0=700v, 1=150v, 2=300, 3=500, 4=600, 5=750, 6=3k,
7=4.5k, 8=5.25k, 9=9k, 10=15k, 11=18k, 12=30k
58 Generator AC Current Full Scale Setpoint 30058 starting at 0:
75,100,150,200,300,400,600,800,1k,1.2k,1.5k,2k,2.5k,3k,4k
Amps
68 Remote Generator Synchronizer Control (GSP+P only) 30068 (This can be written to) 0=Off, 1=Remote synchronization
test, 2=Automatic synchronization
69 Remote Synchronization Control Readiness (GSP+P
only)
30069 0=Not installed, 1=ready for remote command,
2=Synchronizing switch not in auto, 3=Engine control switch
not in auto, 4 Engine was not started remotely, 5 Engine not
running
70 Generator Synchronizer Control Status (GSP+P only) 30070 Starting at 0: Not installed, Inactive, Semiautomatic
paralleling, Permissive paralleling, Remote synchronization
testing, Synchronizing, Synchronization system alarm or
diag., Remote synchronization testing passed, Dead bus time
delay, Closing to dead bus.
201
ormal Stop Input Status 30201 113=Run, 174=Stop